UPS COVER PS 10K
COVER Online Double-Conversion uninterruptible power supply, with a power rating of 10kVA/10kW. Power modules in 3U size, for mounting in 19' rack cabinet. Freely configurable 3:3/3:1/1:1/1:3 phase configuration.
11-PS-10
CHARACTERISTICS
  | 
  | 
BACKUP TIME
| EBM PS | Load | Backup time [min] | 
| PS 10K | ||
| UPS +2xEBMs (40x9Ah) | 100% | 12 | 
| 75% | 18 | |
| 50% | 29 | |
| 25% | 66 | |
| UPS + 4xEBMs (2x40x9Ah) | 100% | 29 | 
| 75% | 43 | |
| 50% | 66 | |
| 25% | 172.2 | |
| UPS + 6xEBMs (3x40x9Ah) | 100% | 49 | 
| 75% | 66 | |
| 50% | 133.6 | |
| 25% | 255.6 | |
| UPS + 8xEBMSs (4x40x9Ah) | 100% | 66 | 
| 75% | 113.2 | |
| 50% | 172 | |
| 25% | 418.4 | 
TECHNICAL SPECIFICATIONS
| Model | PS 10K | 
| Power factor | 10kVA / 10kW | 
| Phases In/Out | 3:3 | 
| Design | Rack/Tower | 
| Input | |
| Nominal voltage | 220 / 230 / 240 VAC | 380 / 400 / 415 Vac | 
| Voltage range | 100 ÷ 160 VAC @ load 50% - 100%, 160 ÷ 300 VAC @ load 100% 174 ÷ 278 VAC @ load 50% - 100%, 278 ÷ 522 VAC @ load 100%  | 
| Nominal frequency | 50 / 60Hz | 
| Frequency range | 45 ÷ 65 Hz | 
| THDi | <3% | 
| Input power factor | ≥0,99 | 
| Output | |
| Nominal voltage | 220 / 230 / 240 VAC | 380 / 400 / 415 Vac | 
| Power factor | 1,0 | 
| Voltage regulation statis/dynamic | ±1% / ±3% | 
| Nominal frequency | 50 / 60 ± 0,1 Hz | 
| Overload caability | 105% no limit, 125% - 10 min., 150% - 30 s., >150% - 500 ms | 
| Efficiency in OnLine mode | 96% | 
| Efficiency in ECO mode | 98% | 
| Crest factor | 3:1 | 
| Switching time | 0ms | 
| Batteries | |
| Cold start | yes | 
| Type of batteries | VRLA, AGM, gel | 
| Batteries range | 32 - 40 pcs x 12V | 
| Max charging curent | 13A | 
| Charging type | 3 – 8 hours up to 90% capacity (configurable) | 
| Charging cycle | According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control. | 
| Dimensions and weights | |
| Dimensions (S x G x W) | 440 x 680 x 132 (3U) | 
| Weight w/o batteries | 25,0 kg | 
| Signaling and communication ports | |
| Operating status indicator | LCD + audible alarm | 
| Communication | USB, RS232, RS485, Dry in/out, EMBS, EPO, slot SNMP | 
| Environmental conditions | |
| Noise level | <65 dB @ load 100% | 
| Operating temperature for UPS | 0°C ÷ 40°C | 
| Recommended operating temperature | 15 °C ÷ 25 °C | 
| Storage temperature | -20°C ÷ 40°C | 
| Humidity | 0 ÷ 95% (non-condensing) | 
| Cerifications | |
| Interference immunity | EN 62040-2:2018, EN 61000-3-2:2019, EN 61000-3-3:2013+A1:2019 | 
| Safety | EN 62040-1:2019, EN 62040-1-2:2003, 62040-3:2001, CE | 
| Optional accesories | |
| - SNMP card | |
| - AS 400 mini (dry-contact) card | |
| - Environmental sensor (EMD) | |
| - Remote Emergency Power Off button | |
| - External maintenance bypass | |
| - Remote LCD panel | |
Due to constant product improvement all specifications are subject to change without notice.
- Apparent power [kVA]
 - 10
 - Active power [kW]
 - 10
 - Technology:
 - VFI-SS-111 (OnLine DoubleConversion)
 - Phase In/Out:
 - 1:1,3:1,3:3,1:3
 - Output PF:
 - 1
 